The 4 onboard NACs must be programmed to tell the horns and strobes how to behave. Go to (Addresses B01 through B04).
Max 159 detectors (smoke/heat) and 159 modules (monitor/control/relay).
Sets a timer (e.g., 24 hours) to resound the panel buzzer if a system trouble condition is silenced but not resolved.
Quick on-site adjustments, adding or deleting individual field devices, checking status codes, and executing emergency troubleshooting when a laptop is unavailable. 2. Navigating the Programming Menu honeywell notifier nfs-320 programming manual
Execute a functional test on at least one device per zone to verify that the corresponding output triggers exactly as mapped in the CBE logic.
| Feature | Program Change (Keypad) | VeriFire® Tools (PC Software) | | :--- | :--- | :--- | | | Quick edits, adding a few devices, walk test, troubleshooting | Full system configuration, major changes, backups, complex logic | | Speed | Slower for large data entry | Very fast; uses a full keyboard and mouse | | Convenience | On-site, immediate changes | Offline programming possible; can create a database at your desk | | Capabilities | Complete control via menu system | All keypad functions plus file management, printing, and simulation | | Cost | Included with the panel | Requires purchase of a license from Honeywell/Notifier |
Keep copies of the .vft database file securely stored on a cloud drive and on-site inside the panel cabinet enclosure. The 4 onboard NACs must be programmed to
This is often the first step in a new installation to quickly establish basic fire protection.
Set type codes such as CONTROL for standard Notification Appliance Circuits (NACs) or RELAY for dry-contact functions like elevator recall or door holder releases. Phase 4: Custom Alpha-Numeric Labeling
This is where you'll spend most of your time. The options are numbered and include: Sets a timer (e
This feature enables the panel to look at adjacent smoke detectors simultaneously. If two neighboring sensors show a slight increase in smoke levels—even if neither has reached its individual alarm threshold—the panel analyzes the combined data to trigger an early warning alarm. 5. Troubleshooting Common Programming Errors
: You should always change the default passwords after you've completed your initial programming to secure the system.